3.TROUBLESHOOTING AND ACTION TROUBLESHOOTING B-65285EN/03
- 110 -
3.3.8 Other Alarms
(Alarm identification method)
#7 #6 #5 #4 #3 #2 #1 #0
<5> Alarm 5
OFS MCC LDM PMS FAN DAL ABF
OFS DAL ABF Alarm description Action
1 Feedback mismatch alarm 1
1 Excessive semi-full error alarm 2
1 Current offset error alarm 3
(Action)
Action 1: This alarm is issued when the move direction of the position
detector is opposite to the move direction of the speed
detector. Check the rotation direction of the separate
detector. If the rotation direction of the separate detector is
opposite to the rotation direction of the motor, take the
following action:
For a phase A/B detector: Reverse the connections of A and
A.
For a serial detector: Reverse the setting of the signal
direction of the separate detector.
In the Series 90B0/G(07) and subsequent editions, the
following settings enable signal directions in the A/B phase
detector to be inverted.
#7 #6 #5 #4 #3 #2 #1 #0
No. 1960 (FS15i)
RVRSE
No. 2018 (FS16i)
RVRSE (#0) Reverses the signal direction of the separate detector.
0: Does not reverse the signal direction of the separate detector.
1: Reverses the signal direction of the separate detector.
If a large distortion exists between the motor and separate detector, this
alarm may be issued in the case of abrupt acceleration/deceleration. In
such a case, modify the detection level.
#7 #6 #5 #4 #3 #2 #1 #0
No. 1741 (FS15i)
RNLV
No. 2201 (FS16i)
RNLV (#1) Modifies the feedback mismatch alarm detection level.
1: Detected with 1000 min
-1
or more
0: Detected with 600 min
-1
or more