B-65285EN/03 START-UP PROCEDURE 4.CONFIRMATION OF THE OPERATION
- 47 -
4.3.6.4 Specifying data to be monitored
<1> Press the four setting switches at the same time for at least a
second ."FFFFF" will be displayed on the indicator.
<2> Turn off the switches and press the "MODE" switch. "d-00" will
be displayed on the indicator and the system will enter the mode
for monitoring internal data.
<3> In this mode, the motor can be operated normally.
Press the "UP" or "DOWN" switch while holding down the
"MODE" switch. The indicator display will change in the range of
"d-00" to "d-12".
<4> The following shows the correspondence between the
destinations of the internal data of the serial spindle and addresses
d-01 to d-12.
d-01 to d-04: Specifies the amount of data to be output to the
indicator, data shift, and output format (decimal
or hexadecimal).
d-05 to d-08: Specifies the amount of data to be output to the
channel 1, data shift, and whether an offset is
provided.
d-09 to d-12: Specifies the amount of data to be output to the
channel 2, data shift, and whether an offset is
provided.
<5> Select address d-xx in the procedure for setting data described in
<3>.
<6> Turn off the "MODE" switch. "d-xx" will disappear 0.5 second
later, and the data will be displayed for a second.
Change the set data using the "UP" or "DOWN" switch within the
second the data is displayed.
<7> When more than a second elapses without pressing the "UP" or
"DOWN" switch, data cannot be changed.
If the "MODE" switch is turned on or off, however, setting can be
started from the beginning of the step in item <6>.