4.CONFIRMATION OF THE OPERATION START-UP PROCEDURE B-65285EN/03
- 32 -
4.3.2.2 The STATUS display is blinking with "--."
(1) When no spindle communication alarm message is indicated on
the CNC
Check whether the CNC software option setting or bit setting is
correct.
(2) When a communication alarm message is indicated on the CNC
No. Cause of trouble Check method Action
1 The cable is incorrect.
Note that the cable used for
connecting an electric/optical
adapter and the cable
connected directly to the
CNC differ in specifications.
Replace the cable with a
correct cable.
2 The cable is defective.
Check the connector housing
section.
Repair or replace the cable.
3
The printed circuit board is
defective.
Replace the unit.
(3) When Dual Check Safety is in use, and No. 756 or 766 occurs on
the CNC (FS16i)
Check that K76, shown below, is mounted on the second spindle.
If Dual Check Safety is not in use or the CNC has only the first
spindle, K76 is unnecessary.
SPM
(First spindle)
CNC
JA41 JA7B JA7A JA7B
K76
JA7A
SPM
(Second
spindle
X2NDSP
0V
(15)
(13)
K76
20-pin half-pitch
connector
Details of K76