B-65150E/04 4. SERVO FUNCTION DETAILS
− 223 −
Parameter setting procedure (4)
Procedure (4) can be used to set parameters according to the cooling
method used for linear motors.
Change the following parameters as listed in Table 4.14.1 (f). For
self-cooling linear motors, the parameters need not be set here, because
they are set up at initialization in procedure (1).
1877
−
OVC alarm parameter (POVC1)
2062
−
1878
−
OVC alarm parameter (POVC2)
2063
−
1893
−
OVC alarm parameter (POVCLMT)
2065
−
1979
−
Current rating parameter (RTCURR)
2086
−
Table 4.14.1 (f) Setting OVC and current rating parameters by cooling
method
Model Cooling
method
Continuous
thrust (N)
POVC1 POVC2 POVCLMT RTCURR
1500A Self-cooling 355 32698 873 2590 1184
3000B Self-cooling 600 32698 873 2590 1184
3000B Air-cooled 720 32667 1257 3729 1421
3000B Water-cooled 1200 32490 3481 10358 2369
6000B Self-cooling 1200 32698 873 2589 1184
6000B Air-cooled 1440 32667 1257 3729 1421
6000B Water-cooled 2400 32490 3481 10358 2369
9000B Self-cooling 1800 32708 744 2207 1093
9000B Air-cooled 2160 32682 1071 3177 1311
9000B Water-cooled 3600 32531 2968 8826 2186
15000C Self-cooling 3000 32730 471 1396 869
15000C Air-cooled 3600 32714 678 2010 1043
15000C Water-cooled 7000 32563 2557 7601 2029