6. HARDWARE
217
D Rotary switch
1) Setting of ROTARY SWITCH in case of connecting to PC or PANEL i
The power–on start sequence can be modified using rotary switch on
the board.
setting of rotary
switch
Description
0 Setting for maintenance.
The start menu is displayed. It is possible to start boot
and IPL from the PC or PANEL i.
1 Setting for usual operation.
The start menu is not displayed.
It is impossible to start boot or IPL from the PC or PAN-
EL i.
2 The CNC and PC or PANEL i are started independently
of each other without handshake.
* CNC
CNC is available if PC or PANEL i is not turned on or
not connected.
(Display for CNC and MDI or Operation panel etc.
are needed to operate.)
The start menu is not displayed if PC or PANEL i is
connected and turned on.
* PC or PANEL i
The start menu is not displayed and it is impossible
to start boot or IPL from the PC or PANEL i if CNC is
connected and turned on.
This setting makes PC or PANEL i or CNC be able to
be turned on/off the power individually if HSSB device
driver for Windows 95/98, NT4.0 or 2000 is installed.
In case of Multi–connection (connecting some CNCs to
one PC or PANEL i), please set to this setting usually.
NOTE PANEL i used here represents hardware that can operate on a
stand–alone basis (provide a stand–alone option).