7. PARAMETERS
317
03260 Two LCD units are connected
#0 LCH : At power–up, the function to connect two LCD
units selects, MDI of the LCD unit specified in
PRM3270(0)/MDI of the LCD unit that was last
selected, before power–down(1)
PRM3270,
3271
03270 Number of the LCD unit of which MDI is
selected at power–up
PRM
3260#0
03271 Number of the LCD unit of which MDI is being
selected
Setting/displayed value = 0: First unit/1: Second unit
03290 Protect of data input
#0 WOF: Input of a tool wear compensation value with
MDI keys is not inhibited (0)/inhibited (1)
#1 GOF : Input of a tool geometry compensation value
with MDI keys is not inhibited (0)/inhibited (1)
#2 MCV : Input of Macro variables with MDI keys is, not
inhibited (0)/inhibited (1)
#3 WZO: Input of workpiece origin offset with MDI keys
is not inhibited (0)/inhibit (1)
#4 IWZ : During operation, workpiece origin offset and
workpiece shift value modification are enabled
(0)/disabled (1).
#6 MCM: Macro variable input from the MDI panel is
enabled regardless of which mode is set (0)/
enabled in MDI mode only.
#7 KEY : The KEY1 to KEY4 signals are used (0)/KEY1
is used for program protection (1).
03291 Memory protection
#0 WPT : The input of the tool wear offset amount is
enabled according to signal KEY1 (0)/enabled
regardless (1)
M series
03292 Data input protection
#7 PKP : The KEYPRM signal (memory protection
signal, parameter write setting) is,
Disabled(0)/Enabled(1)
03294 Start number of tool offset values whose input
by MDI is disabled
03295 Number of tool offset values (from the start
number) whose input by MDI is disabled
KEYPRM
<QG0369 >