2.EXPLANATION OF OPERATION MODES FANUC AC SPINDLE MOTOR αCi series B-65280EN/05
- 442 -
15i 16i 30i
3065 4065 4065
Spindle position gain on servo mode/spindle synchronous control (HIGH)
CTH1A=0, CTH2A=0
3066 4066 4066
Spindle position gain on servo mode/spindle synchronous control
(MEDIUM HIGH) CTH1A=0, CTH2A=1
3067 4067 4067
Spindle position gain on servo mode/spindle synchronous control
(MEDIUM LOW) CTH1A=1, CTH2A=0
3068 4068 4068
Spindle position gain on servo mode/spindle synchronous control (LOW)
CTH1A=1, CTH2A=1
Unit of data : 0.01sec
-1
Valid data range : 0 to 32767
Standard setting value : 1000
These parameters set a position gain on servo mode (rigid
tapping/spindle positioning) or spindle synchronous control.
A parameter is selected according to the input signals CTH1A and
CTH2A.
NOTE
For velocity loop gain setting on spindle synchronous
control and servo mode, the common parameters
are used.
15i 16i 30i
3073 4073 4073
Grid shift amount on servo mode
Unit of data : 1 pulse (=360°/4096)
Valid data range : 0 to 4095
Standard setting value : 0
This parameter is used to shift the reference position on servo mode
(rigid tapping/spindle positioning).
The reference position of the spindle is shifted in the CCW direction
by the specified number of pulses.
15i 16i 30i
3074 4074 4074
Reference position return speed on servo mode
Unit of data : 1min
-1
Valid data range : 0 to 32767
Standard setting value : 0
To perform a reference position return operation, set a reference
position return speed in this parameter.
15i 16i 30i
3085 4085 4085
Motor voltage on servo mode/spindle synchronous control
Unit of data : 1%
Valid data range : 0 to 100
Standard setting value : 60
These parameters set a motor voltage on rigid tapping. Usually, set 60.