11. PROGRAM COMMAND B-63783EN-1/01
- 1164 -
Custom Macro Output Signal
UO000 to UO031<F048 to F051>, UO000 to UO031<F052 to F055>
UO200 to UO231<F056 to F059>, UO300 to UO331<F060 to F063>
[Classification] Output signal
[Function] No function is provided for the control unit. These signals can be read
or written by a custom macro as a type of system variable, and are used
for interface signals between custom macros and the PMC.
These signals correspond to system variables as indicated below.
Signals Q'ty Variables Correspondence of values
UO000
UO001
UO002
UO003
:
UO014
UO015
1
1
1
1
:
1
1
#1100
#1101
#1102
#1103
:
#1114
#1115
"0" at "0" and "1" at "1"
UO000 to UO031 32 #1132 32-bit binary code
*1
UO100 to UO131 32 #1133 32-bit binary code
*1
UO200 to UO231 32 #1134 32-bit binary code
*1
UO300 to UO331 32 #1135 32-bit binary code
*1
*1
Variable value #(1132+n) =
{}
å
=
×−×
30
0
31
31
i
22
i
i
VV
Where Vi=0 when UOni is 0
and Vi=1 when UOni is 1
n : 0 to 3
These system variables can be used on the left side of an assignment
statement as well as on the right side.
The value assigned to the system variable used on the left side last is
used for the value of the system variable to be assigned on the right
side.
Cumulative cutting time count request signal CCT<G045#6>
[Classification] Input signal
[Function] This signal requests to count the cumulative cutting time during
automatic operation.
[Operation] When this signal is "1" and parameter CTM (bit 4 of parameter No.
7710) is 1, the cumulative cutting time set in parameters (Nos. 103 and
104) are counted unconditionally.