1.AXIS CONTROL B-63783EN-1/01
- 128 -
Parameter
#7 #6 #5 #4 #3 #2 #1 #0
1815 APC APZ
[Input type] Parameter input
[Data type] Bitaxis
NOTE
If this parameter bit is changed, the power must be turned off and
back on for the change to take effect.
# 4
# 4 # 4
# 4 APZ
APZAPZ
APZ If an absolute-position detector (absolute-pulse coder) is used as the
position detector, the correspondence between the machine position and
the position of the absolute-position detector is:
0: Not completed.
1: Completed.
If using an absolute-position detector, set this parameter bit to 0 during the first
installation or when the absolute-position detector is replaced, then turn the power
off and back on and set the origin of the absolute-position detector by means of
manual reference position return, etc. This completes the correspondence between
the machine position and the position of the absolute-position detector,
automatically setting this parameter bit to 1.
If the setting of any of the following parameters is changed, the origin must be set
again, so that this parameter bit is automatically set to 0.
- Parameters requiring that the origin be set again after their settings are changed:
1816,1820,1821,1822,1850,1879,1896,1977,1978,2622
# 5
# 5 # 5
# 5 APC
APCAPC
APC Indicates whether the position detector is
0: a detector other than an absolute position detector.
1: an absolute position detector (absolute pulse coder).