3.MANUAL OPERATION B-63783EN-1/01
- 358 -
3.3 MANUAL HANDLE CONNECTED TO I/O LINK
General
Instead of an ordinary manual handle connected to the main CPU board,
a manual handle connected to the I/O Link (operator's panel unit,
distributed I/O) can be used.
- Method of setting I/O-Link-connected manual handles
The method of setting I/O-Link-connected manual handles is described
below.
(1) Select an interface for each handle by using the corresponding
parameter as indicated below.
01
ParameterIH1
(No.2070#0)
The first manual handle is
connected as usual.
The first manual handle is
connected to the I/O Link.
ParameterIH2
(No.2070#1)
The second manual handle
is connected as usual.
The second manual handle
is connected to the I/O Link.
ParameterIH3
(No.2070#2)
The third manual handle is
connected as usual.
The third manual handle is
connected to the I/O Link.
(2) Set the address value (PMC X address) of each manual handle in
the corresponding parameter (No. 2071 through No. 2073).
(3) Turn on the power again.
The I/O-Link-connected manual handles are enabled.
If an incorrect address is specified in step (2), 0 is automatically
set for interface selection in bits 0 to 2 of parameter No. 2070, and
-1 is automatically set as the address value in parameter No. 2071
to No. 2073. Thus, the use of the I/O-Link-connected manual
handles is disabled.
CAUTION
If I/O-Link-connected manual handles cannot be
enabled when the power is turned on again, check
whether bits 0 to 2 of parameter No. 2070, and
parameter Nos. 2071 to No. 2073 are set correctly.