B-63783EN-1/01 9.SPINDLE FUNCTION
- 811 -
- Analog spindle
#7 #6 #5 #4 #3 #2 #1 #0
5603 NDP
[Input type] Parameter input
[Data type] Bitspindle
# 7
# 7 # 7
# 7 NDP
NDPNDP
NDP Specifies whether to make a position coder disconnection check when an
analog spindle is used.
0: Make a check.
1: Do not make a check.
(Valid when bit 3 (NAL) of parameter No. 5602) is set to 0)
Set this parameter to 1 if no position coder is installed when an analog
spindle is used.
5613 Compensation value for the offset voltage of the spindle speed analog
output
[Input type] Parameter input
[Data type] Integerspindle
[Unit of data] Velo
[Valid data range] -1024 - 1024
Set the compensation value for the offset voltage of the spindle speed analog
output.
[Adjustment] To make adjustment, follow the procedure explained below:
(1) Set the standard setting 0.
(2) Specify the spindle speed at which the spindle speed analog output becomes 0.
(3) Measure the output voltage.
(4) Set the value obtained from the following equation in the parameter.
(5) After setting the parameter, specify the spindle speed again at which the
spindle speed analog output becomes 0, then check that the output voltage is 0
V.
12.5
(V) voltagemeasured8191
Setting
×−
=