B-70255EN/01 APPENDIX E.CONTROL SEQUENCES IN LASER OSCILLATOR
- 245 -
E.1 OUTLINE OF LASER OSCILLATION SEQUENCES
SEQ 0
PURGE = 0
LRDY = 0
PTLP = 0
LSTR = 0
SEQ 10
PURGE = 1
LRDY = 0
PTLP = 0
LSTR = 0
SEQ 20
PURGE = 0
LRDY = 1
PTLP = 0
LSTR = 0
SEQ 30
PURGE = 0
LRDY = 0
PTLP = 1
LSTR = 1
CNC POWER ON CNC POWER OFF
(START KEY)
RUN ON
START KEY
RUN OFF
HV OFF
HV ON
SEQ19(WAIT=1)
SEQ29(RFHV=1)
SEQ11(WAIT=1)
SEQ21(RFHV=0)
INITIAL
READY OF DISCHARGING
READY OF OSCILLATION
As is shown in the flow chart, the laser oscillation sequences can be
divided into four steps.
Throughout this description the following notations are used.
Descriptions of the signals used in the figure
RUN : Oscillator start switch
PURGE : Purge in tube completion signal
LRDY : Discharge preparation completion signal
PTLP : Warning light signal
LSTR : Oscillation preparation completion signal
[SQ0] POWER OFF state
This is the state prior to power on where all the signals are in off
state.
[SQ10] INITIAL state
After power is turned on, laser comes into PURGE=1 state. This
signal is on when atmospheric pressure sensor monitors that the intra-
tube pressure equals atmospheric pressure.