B-70255EN/01 6.TROUBLESHOOTING
- 79 -
ALM No.4095
A/D CONVETER-3
This alarm is issued when A/D converter 3 does not return the
conversion completion signal in the specified time after the
converter starts conversion. This A/D converter is designed for
reading the amount of tracing displacement.
ALM No.4096
UNDER TRACING
This alarm is issued when an attempt is made to change the trace
axis by using the trace axis selection function during tracing
control.
ALM No.4097
TRACE AXIS SELECT
This alarm is issued when two or more trace axis selection
signals are specified using the trace axis selection function.
ALM No.4098
TRACE AXIS & PLANE
This alarm is issued when no plane is selected for the trace axis.
ALM No.4099
GAS PRES.NOT REACH
This alarm is issued, if the discharge tube gas pressure does not
reach [specified discharge tube gas pressure during oscillation -
tolerance] after HV is set to ON.
Alarm output condition
The gas pressure at the start of discharge is increased to the gas pressure
level for oscillation. Then, when the actual gas pressure does not rise to the
value obtained by subtracting the value set in parameter No. 15248 from the
value in parameter No. 15242 or 15243 within 15 seconds after the gas
pressure for oscillation is set as the target gas pressure level, this alarm is
issued if bit 3 of parameter No. 15001 is set to 1.
Related parameters
PRM.15001#3
Specifies whether to preset the integral value of gas pressure control.
PRM.15242,15243 Intra-tube pressure for oscillation
PRM.15248
Tolerable amount by which the target gas pressure is not reached
Cause of trouble Solution
1 Invalid parameter
setting
Check whether the values of PRM Nos. 15001/bit 3,
15247, and 15248 are set as indicated in the attached
data sheets. If a different value is set, set the value
specified in the data sheets.