B–64115EN/01
4. INTERFACE BETWEEN CNC AND PMC
287
#3 (TRNSRAM): 0: After on-line editing, the ladder program is not automatically
transferred to the backup RAM.
1: After on-line editing, the ladder program is automatically transferred
to the backup RAM.
#4 (CALCPRTY): 0: The built-in programmer function calculates the RAM parity.
1: The built-in programmer function does not calculate the RAM parity.
#5 (CHKPRTY): 0: The system performs parity check for the system ROM, program
ROM and program RAM.
1: The system does not perform parity check for the system ROM,
program ROM, or program RAM.
#6 (EDITLAD): 0: The editing of a sequence program is disabled.
1: The editing of a sequence program is enabled.
#7 (IGNDINT): 0: The system initializes the LCD when the screen is switched to the
PMCMDI screen.
1: The system does not initialize the LCD when the screen is switched to
the PMCMDI screen.
: This flag is useful when a user program is used. When the screen is
switched to the PMCMDI screen, PMC control software determines
whether the system initialize the LCD, by checking this flag. When
this flag is on, an application program must initialize the LCD.
#7
PTCTPRMK019
#6
HIDEPRM
#5 #4 #3 #2
ALWSTP
#1
C–REJECT
#0
FROM–WRT
#0 (FROM_WRT): 0: After editing a ladder or C program, does not automatically write it to
F–ROM.
1: After editing a ladder or C program, automatically writes it to
F–ROM.
#1 (C-REJECT): 0: The system activates a C program.
1: The system does not activate a C program.
#2 (ALWSTP): 0: The execution/stop operation of a sequence program is disabled.
1: The execution/stop operation of a sequence program is enabled.
#6 (HIDEPRM): 0: The display of PMC parameters and the output of PMC parameters to
the outside are enabled.
1: The display of PMC parameters and the output of PMC parameters to
the outside are disabled.
#7 (PTCTPRM): 0: The modification and reading of PMC parameters are enabled.
1: The modification and reading of PMC parameters are disabled.
CAUTION
Set all unused bits to 0.