B–61803E–1/10
D. MACRO COMPILER/MACRO
EXECUTOR WITH CAP I (Series 16/18)
APPENDIX
257
= 0: Expanded conversational macro exclusive
variables at the #20000 level have floating
decimal point format (Be sure to set 0)
9003 10000000
bit 7 = 1: Special function for CAP valid
= 0: Special function for CAP not valid
(Be sure to set 1)
bit 3 = 1: 14” color CRT
= 0: 9” monochrome/color CRT
9007 0100000
bit 6 = 1: FS16-TA CAP I is valid
= 0: FS16-TA CAP I is invalid
9033 97
Dedicated data for CAP
9037 7
Dedicated data for CAP
9044 2044
Dedicated data for CAP Set this value unconditionally for
either case of part program memory of 120 m or 320 m.
5. Setting parameters for FS16-MA
8000 10000000
bit 0 = 1:The program of the block containing M99 ends
= 0: The program of the block containing M99 does
not end (Be sure to set 0)
bit 1 = 1:The program of the block containing M02 ends
= 0: The program of the block containing M02 does
not end (Be sure to set 0)
bit 2 = 1:The program of the block containing M30 ends
= 0: The program of the block containing M30 does
not end (Be sure to set 0)
8010 00000001
bit 0 = 1: Corresponds to macro executor having CAP
= 0: Corresponds to the standard macro executor
(Be sure to set 1)
8011 16MA,
****
, EXC2/
**
Specifies the file name of macro executor 2.
However, as ‘16MA.****.EXC2/**’ is different
depending on the macro executor used, refer to the Table of
Specifications of FAPT MACRO COMPILER (MACRO
EXECUTOR) with CAP in Section 2, then input the file
name of the macro executor to be used.
Example)
The file name when using the FS16-MA monochrome high
resolution CRT is ”16MA.BA21.EXC2/02”.
9000 10010000
bit 4 = 1: Allows use of a macro cassette of 1M Kbyte
capacity
= 0: Allows use of a macro cassette of other than 1M
Kbyte capacity (Be sure to set 1)