FANUC AC SPINDLE MOTOR a series
2. FUNCTION EXPLANATION
B–65160E/02
158
16i/16 #7 #6 #5 #4 #3 #2 #1 #0015i15
DS5 DS4 DS3 DS2 DS1
6513 3013 3013 4013
6653 3153
1st–
2nd–
(MAIN side)
DS5 DS4 DS3 DS2 DS1
6153 3333 3189 4189
6333 3553
1st–
2nd–
(SUB side)
DS5 to DS1:
Current dead zone data
This parameter data is determined by the amplifier being used.
When spindle switching control is used, a nonstandard amplifier, which
does not match the motor, may be used.
In such a case, modify the data according to the amplifier being used.
Note that if invalid data is set, the switching element of the power circuitry
may be damaged.
DS5 DS4 DS3 DS2 DS1 Amplifier model
0 0 1 1 0 SPM–2.2 to SPM–15
0 1 0 0 1 SPM–22 to SPM–30
0 1 1 1 1 SPM–45
16i/1601515i
Speed zero detecting level (MAIN side)
6524 3024 3024 4024
6664 3164
1st–
2nd–
Speed zero detecting level (SUB side)
6763 3343 3199 4199
6343 3563
1st–
2nd–
Data unit : 0.01%
Data range : 0 to 10000
Standard setting : 75
This data is used to set the detecting range of speed zero detection
signal (SSTA).
When the motor speed reaches (setting data/100)% or less of maximum
speed, the bit of speed zero detection signal (SSTA) is set to ”1”.
16i/1601515i
Current conversion constant (MAIN side)
6610 3110 3110 4110
6750 3250
1st–
2nd–
Current conversion constant (SUB side)
6228 3408 3264 4264
6750 3628
1st–
2nd–
Data unit :
Data range : 0 to 32767
Standard setting : Depends on the motor model.
When spindle switching control is used, a nonstandard amplifier, which
does not match the motor, may be used.
In such a case, modify the setting of this parameter according to the
conversion formula below.