14/42
SHEETDESCRIPTIONDESIGN DATE EDIT
01 Mutai Newl
re
istered
TITLE: Additional explanation of
PROFIBUS-DP Master function
(I/O Module Assignment function)
B-62924EN/04-1
FANUC LTD.
02.10.7
DRAW.NO.
CAUTION
When assigning PROFIBUS data to PMC address, please note the
following.
(1) Only PMC R address area is available.
(When using PMC-SB5, PMC-SB6 or PMC-NB6, more than
R2999 can not be configured.
(2) Ensure that a specified DI data area, DO data area, and
Diagnostic data area do not overlap one another.
(3) Ensure that the specified addresses do not overlap a work area
used for a ladder program.
NOTE
The slot number “NSL” should be inputted by manual even when the
Profibus parameters are configured automatically by using Softing’s
Configurator.
(2)The following soft keys are available.
[ENABLE]:
This key makes the selected slave available. An available slave is marked with “*” at
the position of the slave number “NO” on the screen.
[DISBLE] :
This key annuls the selected slave.
[ NO.AT ] :
This key assigns slave numbers with a serial to the slave which the cursor is located
on and the following slaves.
[ ADR.AT ] :
This key assigns addresses to the selected slave and the following available slaves.
For example, with the situation that the values are inputted like Screen 1-5, when
this key is pushed at the position of IDX 7, DGN_ADDRs of IDX08-10 will be
configured automatically as R1506, R1512, R1518 respectively.
[ INIT ] :
This key initializes the parameter values of the selected slave, including the slave
parameter and DI/DO address assignment.