1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
- 22 -
Table 1-3 Bus Parameter Settings Corresponding to Each Transfer Rate
Bus parameter Setting
1: FDL ADD 0 to 125
2: BAUDRATE (Kbps) ≤187.5 500 1500 3000 6000 12000
3: T SL 100 200 300 400 600 1000
4: MIN T SDR 11 1111111111
5: MAX T SDR 60 100 150 250 450 800
6: T QUI 0 00369
7: T SET 1 1 1 4 8 16
8: TTR 65000 65000 65000 65000 65000 65000
9: G 10 1010101010
10: HSA 126 126 126 126 126 126
11: MAX RETRY 1 11234
12: BP FLAG 0 0 0 0 0 0
13: MIN SLAVE INT 1 1 1 1 1 1
14: POLL TIME OUT 1000 1000 1000 1000 1000 1000
15: DATA CONTROL 100 100 100 100 100 100
16: CLASS2 NAME This parameter need not be set.
17: MASTER USER DATA 0 0 0 0 0 0
Viewing this table for parameter setting:
First, determine the value of 2: BAUDRATE. Then, set the other parameters according to
the set baud rate.
NOTE
For multiple master communication, satisfy the
following conditions:
- The value set for 1:FDL ADD for a master station is
not used as another master station number.
- The same values are set for bus parameters 2 to 11
for all master stations.
- When a larger value is set for T SET, T SL is larger
than T ID1.
(T ID1 = 33 + 2 + 2 × T SET + T QUI)