27/42
SHEETDESCRIPTIONDESIGN DATE EDIT
01 Mutai Newl
re
istered
TITLE: Additional explanation of
PROFIBUS-DP Master function
(I/O Module Assignment function)
B-62924EN/04-1
FANUC LTD.
02.10.7
DRAW.NO.
[ ADR.AT ] :
This key assigns the serial address to the slave which the cursor is located on and the
following slaves.
For example, in Screen 1-8, when this key is pushed at the position of SLT 00 of NO
7 (Slave number 7), each DI/DO_ADDR of SLT01-03 will be configured
automatically as R0204/R0704, R0208/R0708 and R0212/R0712.
Module data setting
In general, the selectable modules are listed in the GSD file of a slave. Please select the
appropriate data from the [Module] list of the GSD file, corresponding to the I/O module
unit you use, and configure the parameter to Screen 1-9 as a module data.
A module data of Screen 1-9 can be inputted as follows.
Example)
This example explains the way of configuring the following I/O module units like NO 3
(Slave number 3) of Screen 1-8.
[ Types of the installed I/O modules into the slave station (NO.3) ]
Basic Module No input/output interface
I/O Module (Type A) Input : one byte , Output : one byte
I/O Module (Type B) Input only : one byte
[Position of Modules on Slave station 3]
Basic module
I/O Module
(TYPE A)
I/O Module
(TYPE B)
I/O Module
(TYPE A)
Slot number 0 Slot number 1 Slot number 2 Slot number 3
Here, the GSD file is assumed to be described as follows.
・
・
Module = ” NO I/O ” 0x00
EndModule
Module = ” TYPE A” 0x10, 0x20
EndModule
Module = ” TYPE B ”
EndModule
・
・
The contents (a part) of GSD file