1.16i/18i/21i-A/B, Power Mate i-D/H, AND 16/18-C OPERATION B-62924EN/04
- 32 -
NOTE
For the operation mode, pay careful attention to the
following points:
(1) When the power is turned on in the status in which
at least one slave station is ACTIVE, the master
station automatically starts in the OPERATE mode.
An ACTIVE slave station means a slave station for
which ENABLE and SLAVE TYPE = 192 are set as
slave parameters.
(2) In a case other than (1), that is, when the power is
turned on in the status in which all slave stations
are not ACTIVE, the master station automatically
starts in the STOP mode.
(3) A FANUC master station cannot manually be put in
the OFFLINE mode.
If a FANUC master station is in the OFFLINE mode
immediately after power-on, an error may occur.
See Table 1-1, "Setting Error Message."
A message may be displayed at the lower left of Screen 1-8. In this
case, take appropriate action, referencing the table below.
Table 1-6 Mode screen message
Message Caution and action
“MODE SET OK” Mode setting was performed normally.
“INVALID OPERATION”
Mode setting was performed in an invalid order.
(For example, the order is [OPERATE] and
[STOP].)
Perform mode setting in a valid order as
described above.
"POWER MUST BE OFF"
This message is displayed if one of the
following three operations is performed:
1) [STOP] and [OFFLINE] are set in this order.
2) The power is turned on in the status in which
no slave stations are ACTIVE, and [STOP]
and [CLEAR] are set in this order.
3) After slave parameters are downloaded from
a class-2 master station, [STOP] and
[CLEAR] are set in this order.
In case 1), the OFFLINE status is equal to the
power-off status.
In case 2) or 3), if settings are changed by
downloading from the slave parameter setting
screen or class-2 master station after power-
on, the change cannot be made take effect
immediately. For this reason, turn the power
off, then on again.