B-63330EN/03 4.DESCRIPTION OF PARAMETERS
- 37 -
0024 Assignment of the communication with the PMC Ladder development tool
(FAPT LADDER-II, Ladder editing package)
[Input type] Setting input
[Data type] Integer
[Valid data range] 0 - 255
Assigns the communication with the PMC Ladder development tool
(FAPT LADDER-II, Ladder editing package).
The value of this parameter determines the communication to be
started, as follows:
0: At power-on, communication conforms to the settings on the
PMC setting screen (displayed by selecting [PMC], [SETING],
and the [ONLINE] screen in this order).*1
Communication stops if this parameter is changed from another
value to 0.
1: RS-232-C serial port 1 (JD5A)
2: RS-232-C serial port 2 (JD5B)
3: RS-232-C serial port 3 (JD36A)
4: RS-422 serial port (JD6A)
255: Do not allow communication with the PMC Ladder development
tool.
*1 When using HSSB, set the parameter to 0.
After system startup, communication settings can be changed with
this parameter or on the PMC setting screen.
Refer to the PMC Ladder Language Programming Manual (B-
61863E).
To use the online monitor function of the PMC Ladder development
tool, set the desired communication port number in this parameter.
To transfer sequence programs in offline mode, set this parameter to
"0." In addition, on the PMC [ONLINE] screen, select "NOT USE" in
the "RS-232C" field.
To forcibly stop the communication with the PMC Ladder
development tool, set this parameter to "255."
0031 Initial value used for automatic setting of sequence Nos.
[Input type] Setting input
[Data type] Integer
[Valid data range] 0 - 99999999
0032 Increment used for automatic setting of sequence No.
[Input type] Setting input
[Data type] Integer
[Valid data range] 0 - 99999999
If the increment is set to 0, no sequence Nos. are inserted.