2. 15i SERIES HARDWARE
B–63785EN/01
152
If an error occurs, the LEDs repeatedly flash ”LONG” then ”SHORT.”
(For ”LONG,” the LED lights for a long time. For ”SHORT,” the LED
lights for a short time.)
STATUS LED
indication
No.
LONG
1 2 3 4
SHORT
1 2 3 4
Fast Ethernet/Fast data server state
1 J J j j j j J J SDRAM paruty alarm
2 j j J J j j j j
Failure caused by this
board
General invalid instruction
3 J j J j j j j J
Invalid slot instruction
4 J J j j j j j J
Failure caused by
another board
NMI of another module
NOTE
If an error, indicated by repeatedly flashing a LONG and
SHORT combination other than the above, occurs, contact
FANUC.
No. LED indication Fast Ethernet board state
1 ALM J Parity error occurred in main memory.
No. LED indication Fast Ethernet communications status
1 COM J Lights when data is sent.
3 LIL J Lights when a connection is made correctly with the hub.
4 COL J Lights if a data collision occurs.
5 BTX J Lights when a connection is made with 100BASE–TX.
NOTE
LIL: Communication is not performed while this LED is not lit.
A probable reason for this is that the Fast Ethernet/Fast
data server is not properly connected to the hub, or that
the hub is off. This LED should be lit at all times while the
Fast Ethernet is properly connected to the hub.
COL: This LED lights frequently if there is excessive traffic on
the communication line or if there is excessive peripheral
electrical noise.
On the board, the setting pins (TM4, TM5) are installed. Connect each
jumper plug to side A (factory–set state). Do not remove a jumper plug,
and do not change the setting of a jumper plug. Otherwise, the board does
not operate normally.
D STATUS LED indications
if an error occurs
D ALARM LED indications
if an error occurs
D LED indications related
to communication status
D Setting pins