The time from disconnecting the cable of old battery to connecting the
cable of new battery should be shorter than 5 minutes.
BIOS settings are not erased when bellow procedures are done correctly. But if BIOS settings
are erased, following massage is displayed at power–on, default BIOS settings are loaded and
restart.
“251: System CMOS checksum bad – Default configuration used.”
Therefore, please check whether BIOS settings were changed from default settings or not
before exchanging battery. And, if this message is displayed unfortunately, you should modified
BIOS setting.
(1) After CNC display unit with PC functions is turning on for 5 seconds
or more, turn off the power of CNC display unit with PC functions,
then enable to work from rear side of CNC display unit with PC
functions by taking it out from panel, etc.
(2) Pull out battery connector (BAT1), then remove the battery from the
holder.
(3) Put the connector (BAT1) of new battery within five minutes, then put
the new battery in the holder.
(4) Mount CNC display unit with PC functions again.
(5) Turn on the power, then confirm that BIOS parameters have not been
erased (confirm that error message is not displayed).
Battery Holder
Lithium Battery
A02B–0200–K102
Connector
(BAT1)
Fig. 2.15.3.1 Exchanging Lithium Battery