7. TROUBLESHOOTING
B–63785EN/01
388
Although the tool is being fed with 128 or more pulses of positional
deviation (DGN3000) in the direction of reference position return, the
one–rotation signal is not received at least once, a reference position
return is performed.
YES
NO
Start
Check whether there are 128 or more pulses of positional
deviation (the value at No. 3000 on the diagnosis screen) in
the return direction during or before reference position return.
ROV1 ROV2
00
01
10
11
Override
value
100%
50%
F1%
Fo feedrate
Positional
deviation: :
DGN 3000
128 or more?
(1) (Go to the next page)
The feedrate is too low. Increase the feedrate.
Check the feedrate command.
PRM 1420 F : Rapid traverse rate [mm/min]
PRM 1825 G : Servo loop gain [0.01sec
–1
]
PRM 1417 R : Rapid traverse rate ratio until manual reference position
return is completed
Positional deviation =
F 5000/3
G Detection unit [µm/PLUSE]
R
100
Detection unit: The amount of travel made per command pulse (normally 1 µm)
When the fractional portion displayed on the position display screen on a milli-
meter machine consists of four digits, the detection unit is 0.1 µm.
Check the rapid traverse override signals.
ROV1 DGN 10065(G006.5)
ROV2 DGN 10066(G006.6)
PRM 1412 Override F1
PRM 1421 Fo feedrate
Check the reference position return deceleration signal.
*DEC1 to *DEC10 DGN 10645 (G064.5, G065.5, ...)
If return operation starts with the deceleration signal set to 0, the feedrate is
set to the FL feedrate.
PRM 1425 FL feedrate
7.7
ALARM PS200
(GRID
SYNCHRONIZATION
ERROR)
Description
Action