7. TROUBLESHOOTING
B–63785EN/01
368
a. In–position check (checking for positioning) is under way.
This implies that axis movement has not been completed. Check
the contents of the following diagnostic number. (It becomes “1”
under the following condition.)
Diagnosis 3000 (position error) > parameter (No. 1827)
(in–position check effective area)
1 Check the parameter settings against the parameter list.
1825 Individual–axis servo loop gain (Standard value : 3000)
2 It is likely that the servo system is abnormal. Make a check by
referring to the descriptions of servo alarms SV023, SV008, and
SV009.
b. The override value for the manual feedrate is 0%.
Check the following signals, using the PMC diagnostic function
(PMCDGN).
#7
*JV7G014
#6
*JV6
#5
*JV5
#4
*JV4
#3
*JV3
#2
*JV2
#1
*JV1
#0
*JV0
#7
*JV15G015
#6
*JV14
#5
*JV13
#4
*JV12
#3
*JV11
#2
*JV10
#1
*JV9
#0
*JV8
If the override value is 0%, all bits at the addresses shown above
become 111.....111 or 000.....000.
c. The interlock/start lock signal is active.
Check the following signal, using the PMC diagnostic function
(PMCDGN).
1 The interlock signal (*IT) is active.
#7
G000
#6 #5 #4 #3 #2 #1 #0
*IT
The interlock signal with *IT = 0 is active.
2 The individual–axis interlock signal (*ITn), servo–off signal
(*SVFn), or control signal detach signal (DTCHn) is on.
#7
DTCH1G064
#6
*SVF1
#5 #4
*IT1
#3 #2 #1 #0
(First axis)
The address for the nth axis is calculated as follows:
64 + (n – 1)*4
The interlock signal with *ITn, *SVFn = 0, and DTCHn = 1 is
active.
3 The automatic operation all–axis interlock (*AIT) or the block
start interlock signal (*BSL) is active.
#7
G001
#6 #5 #4 #3 #2 #1
*BSL
#0
*AIT
The interlock signal with *AIT and *BSL = 0 is active.
4 The cutting block start interlock signal (*CSL) is active.
#7
G000
#6 #5 #4 #3 #2 #1
*CSL
#0
The interlock signal with *CSL = 0 is active.