Series 30i/ 31i/ 32i-MODEL A
PMC Supplemental Programming Manual
01 04.12.27
S. Hasegawa
New registration
B-63983EN/02-3
EDIT
DATE
DESIG.
DESCRIPTION
42/73
DRAW.NO.
5.1 STRUCTURE OF EXTRA RELAY
Modify "2.2.5 Extended Relay Addresses (E)" as follows:
5.1.1 Extra Relay Addresses (E)
The following table lists the number of signals (bytes) that can be used as
extra relays.
Extra relays can be used in the same manner as for internal relays.
Turning on the power clears this area to 0.
30i/31i/32i-A
First PMC
Second PMC
(option)
Third PMC
(option)
Dual-check
safety PMC
(option)
Number of bytes 10000 -
For the multi-path PMC function, this area is common memory. Each
PMC program can send and receive information to/from other PMC
program via this area.
ddress numbe
E0
E1
E9999
76 5 4 32 1 0
.
.
.
NOTE
The extra relay addresses (E) can be optionally
configured as nonvolatile. When they are
nonvolatile, turning off the power does not erase the
memory contents.
System Keep Relays related to Extra Relays
The following system keep relays have influence on managing extra
relays.