B-63983EN/01 2.PMC SPECIFICATIONS
- 113 -
PMC setup parameters
Execution sequence for multiple PMCs
11900 PMC having the first priority in execution sequence
11901 PMC having the second priority in execution sequence
11902 PMC having the third priority in execution sequence
NOTE
Once any of these parameters is re-set, it is
necessary to turn the power off and on again.
[Input type] Parameter input
[Data type] Integer
[Valid data range] 0 to 3
This item specifies the execution sequence for each PMC if the multi-
PMC function is used.
Setting PMC
0 Standard setting (see below)
1First PMC
2 Second PMC
3Third PMC
When all these parameters are 0, the standard execution sequence
setting shown below is used.
First PMC
Second
PMC
Third PMC
Other processing such as
tracing
Fig. 2.4.3 (a) Standard execution sequence for multiple PMCs
CAUTION
If any of these parameters is nonzero, a duplicate or
missing number results in the PMC alarm "ER50
PMC EXECUTION ORDER ERROR", thus disabling
all the PMCs from starting.