4.LADDER LANGUAGE B-63983EN/02
- 220 -
(b) Timer set time address
Sets the first address of the timer set time field.
The continuous 2-byte memory space is required for the timer set
time field.
The data table (field D) is normally used as this field.
TIME
Timer set time + 0
Timer set time + 1
TIME: Timer set time (1 to 32,767)
The timer setting time is converted to the binary format based on
the timer accuracy (in units of 8 msec, 48 msec, etc.).
The timer setting time is shown as follows:
8 msec.................. 8 to 262,136 msec
48 msec................ 48 to 1,572,816 msec
1 sec..................... 1 to 32,767 sec
10 sec................... 10 to 327,670 sec
1 min.................... 1 to 32,767 min
1 msec.................. 1 to 32,767 msec
10 msec................ 10 to 327,670 msec
100 msec.............. 100 to 3,276,700 msec
(c) Timer register address
Set the start address of a timer register area.
A timer register area must be allocated to a continuous four-byte
memory area starting from the set address. The user area (R
area) is used as a timer register area. This area should be used by
the PMC system, and therefore should not be used by the
sequence program.
Timer register + 0
Timer register + 1
Timer register + 2
Timer register + 3
Timer register
Timer relay (W1)
The output W1 is turned on when the time specified in the parameter
of this instruction elapses after ACT is set to 1. The designer can
freely decide the address of W1.