B-63983EN/02 3.I/O LINK
- 159 -
3.2.4 Assignment Method for the Power Mate
To use Power Mate-MODEL D/H, Power Mate i MODEL-D/H, or I/O
Link b amplifier as an I/O Link slave, assign its connection
information on the I/O Link master.
On the I/O Link slave, assignment is not required because the
addresses are fixed.
An example of connection is shown below.
Operator's panel
interface unit
I/O LINK
MASTER
[GROUP] = 0
[GROUP] = 1
[BASE] = 0, [SLOT] = 1
[BASE] = 0, [SLOT] = 1
Power Mate
Assignment method
For the group number, set the group number used in the configuration.
For the base number, always set 0.
For the slot number, always set 1.
Number of input/output
points (input/output)
Input device assignment
name (module name)
Output device assignment
name (module name)
32/32 FS04A FS04A
64/64 FS08A FS08A
128/128 OC02I OC02O
256/256 OC03I OC03O
NOTE
1 Assign input and output module names with the
same number of points.
2 For the I/O Link b amplifier, assign OC02I/OC02O.
Examples of settings
To connect Power Mate-D with 256/256 points in group 1:
Enter 1.0.1.OC03I for input and 1.0.1.OC03O for output.
To connect an I/O Link b amplifier in group 1:
Enter 1.0.1.OC02I for input and 1.0.1.OC02O for output.