Series 30i/ 31i/ 32i-MODEL A
PMC Supplemental Programming Manual
01 04.12.27
S. Hasegawa
New registration
B-63983EN/02-3
EDIT
DATE
DESIG.
DESCRIPTION
46/73
DRAW.NO.
(2) Table control data
Table control data are the data to control the extra relay tables.
Unless these data are properly set, you can not properly view or edit
the contents of extra relay tables described in (3) below.
First, you configure the table control data properly, reffering to the
explanation in this section.
You can reach EXTRA RELAY CONTROL screen by [EXTRA
RELAY] soft key in DATA TABLE CONTROL screen. The soft
key is displayed when 1 is set to the system keep relay K909.5.
(a) Number of table groups
Set number of groups that you are planning to divide the extra
relays. The maximum number is 100.
(b) Table group 1 control data – Table group n control data
Each extra relay table has its table control data. Each table
control data consists of the same items; table start address,
table parameter, data type, and the number of data items.
(i) Table start address
This item decides the start address of the area used for
each extra relay table.
(ii) Table parameter
#7 #6 #5 #4 #3 #2 #1 #0
SIGN HEX MASK COD
COD
0: Data in this table are displayed in binary format.
1: Data in this table are displayed in BCD format.
MASK
0: The contents of this table are not protected.
1: The contents of this table are protected.
HEX
0: Data in this table are displayed in binary or BCD
format. (COD is effective)
1: Data in this table are displayed in hexadecimal
format.
SIGN
0: Data in this table are displayed as signed numbers.
1: Data in this table are displayed as unsigned
numbers.
NOTE
1 The setting of COD (bit 0) is effective when HEX (bit 2)
= 0.
2 The setting of SIGN (bit 3) is effective when COD (bit
0) = 0 and HEX (bit 2) = 0.
(iii) Data type
This item decides the length of data in this table.