B-65270EN/05 4.SERVO FUNCTION DETAILS
- 115 -
<4> Set the current loop gain magnification.
2747(FS15i)
Current loop gain magnification in high-speed HRV current control mode
2334(FS30i,16i)
[Unit of data] %
[Valid data range] 100 to 270
[Recommended value] 150
This parameter is valid only for cutting feed in the high-speed HRV
current control mode.
<5> Set the velocity loop gain magnification.
2748(FS15i)
Velocity loop gain magnification in high-speed HRV current control mode
2335(FS30i,16i)
[Unit of data] %
[Valid data range] 100 to 400
This parameter is valid only for cutting feed in the high-speed HRV
current control mode.
1700(FS15i)
Velocity loop gain magnification (cutting/rapid velocity loop gain switching)
2107(FS30i,16i)
[Unit of data] %
[Valid data range] 100 to 400
This parameter is valid only for cutting feed when the high-speed
HRV current control mode is not set.
<6> Set the high-speed HRV current control mode.
To use servo HRV3 control with servo software Series 90D0 and
90E0 for the Series 30i, 31i, and 32i, set the following bit, which
automatically sets the high-speed HRV current control mode
during cutting feed:
#7 #6 #5 #4 #3 #2 #1 #0
- NOG54
2283(FS30i,31i,32i)
NOG54(#0) The high-speed HRV current control mode (servo HRV3 control) is:
0: Set only when both G5.4Q1 and G01 are specified.
1: Set when G01 is specified (G5.4Q1 is not monitored).
NOTE
This function cannot be used during servo HRV4
control.
<7> This completes parameter setting. To actually enter the
high-speed HRV current control mode, G codes must be
programmed. (This is not required if NOG54 is set to 1. See
Subsection 4.2.3.)
NOTE
The velocity loop gain is changed as listed below
according to whether the high-speed HRV current
control mode is set or not.