B-65270EN/05 3. αiS/αiF/βiS SERIES PARAMETER ADJUSTMENT
- 63 -
(2) Alarms related to the Pulsecoder and separate serial Pulsecoder
(2-1) αi Pulsecoder
These alarms are identified from alarms 1, 2, 3, and 5. The
meanings of the bits are as follows:
Alarm 3 Alarm 5 1 Alarm 2
CSA BLA PHA RCA BZA CKA SPH LDM PMA FBA ALD EXP
Description Action
1 Soft phase alarm 2
1 Zero volts in battery 1
1 1 1 0 Count error alarm 2
1 EEPROM abnormal alarm
1 Voltage drop in battery
(Caution)
1
1 Pulse error alarm
1 LED abnormality alarm
CAUTION
For alarms with no action number indicated, the
Pulsecoder may be defective. Replace the
Pulsecoder.
(2-2) Separate serial detector coder
These alarms are identified from alarm 7. The meanings of the
bits are as follows:
Alarm 7
OHA LDA BLA PHA CMA BZA PMA SPH
Description Action
1 Soft phase alarm 2
1 Pulse error alarm
1 Zero volts in battery 1
1 Count error alarm 2
1 Phase alarm 2
1
Voltage drop in battery
(Caution)
1
1 LED abnormality alarm
1 Separate detector alarm
CAUTION
For alarms with no action number indicated, the
detector may be defective. Replace the detector.
Action 1: Battery-related alarms
Check whether the battery is connected. When the power is
turned on for the first time after the battery is connected, a
battery zero alarm occurs. In this case, turn the power off then on
again. If the alarm occurs again, check the battery voltage. If the
battery voltage drop alarm occurs, check the voltage, then
replace the battery.