2. SETTING αiS/αiF/βiS SERIES SERVO PARAMETERS B-65270EN/05
- 50 -
Alarm
detail No.
Parameter No.
(Series 15i)
Parameter No.
(Series 30i, 16i,
and so on)
Cause Action
10016
10019
1740#0 2200#0
The internal value of a parameter
related to runaway detection
overflowed.
Do not use the runaway detection
function. (Set bit 0 to 1.)
10024
10025
An overflow occurred in internal
calculation on the separate detector
serial feedback extrapolation level.
When servo software Series 90B0
is used, change the software
edition to edition D or a later
edition. (For series other than
90B0, the software edition need not
be changed.)
10033 1809 2004
Illegal control cycle setting
This error occurs if automatic
modification is carried out for the
control cycle.
Correct this parameter related to
interrupt cycle setting.
10053 1960#0 2018#0
When a linear motor is used, the
scale reverse connection bit is set.
When the linear motor is used, the
scale reverse connection bit
cannot be used.
10062 1749#4 2209#4
The amplifier used does not support
the HC alarm prevention function.
When you use the current amplifier
continuously, set the function bit
shown to the left to 0.
When using the HC alarm
prevention function, use an
appropriate amplifier that supports
the function.
10072 1951#6 2007#6
The customer's board function and
FAD were specified at the same time.
The customer's board function and
the FAD function cannot be used
together. Turn off one of them.
10082 2601#6 2213#6
The NC does not support the
improved version of the cutting/rapid
position gain switching function.
Disable this function.
This alarm is issued when an invalid
control cycle is set.
Change the control cycle setting to
HRV1, HRV2, HRV3, or HRV4.
→ See Supplementary 2.
Different control cycles are set within
one servo CPU.
Set the same control cycle for axes
controlled by one servo CPU.
→ See Supplementary 2.
When HRV4 is enabled, a detector
that does not support HRV4 is used.
(FS30i only)
Replace the detector with a
detector supporting HRV4.
Alternatively, disable HRV4.
→ See Supplementary 2.
When HRV4 is enabled, a servo
amplifier that does not support HRV4
is connected. (FS30i only)
Replace the servo amplifier with a
servo amplifier supporting HRV4.
Alternatively, disable HRV4.
→ See Supplementary 2.
10092
1009393
1809
1707#0
1708#0
2004
2013#0
2014#0
HRV1 is set. (FS30i only)
The Series 30i does not allow
HRV1 setting. Set HRV2, HRV3, or
HRV4.
→ See Supplementary 2.
10103
1809
1707#0
2004
2013#0
If a current control cycle of 250 µs is
set, this error occurs when HRV3 is
specified.
Set the control cycle correctly.
→ See Supplementary 2.