B-65270EN/05 4.SERVO FUNCTION DETAILS
- 145 -
<2> Setting for resonance elimination filter 1
Only resonance elimination filter 1 has the conventional specification
if the damping is 0 and the improved specification if the damping is
not 0.
1706 (FS15i)
RE filter 1 : Attenuation center frequency
2113 (FS30i, 16i)
[Valid data range] 250 to 992 (if damping = 0)
96 to 1000(HRV1 or HRV2), 96 to 2000(HRV3), 96 to 4000(HRV4)
(if damping ≠ 0)
[Unit of data] Hz
2620 (FS15i)
RE filter 1 : Attenuation bandwidth
2177 (FS30i, 16i)
[Valid data range] 20, 30, 40 (if damping = 0)
0 to attenuation center frequency (if damping ≠ 0)
[Unit of data] Hz
2772 (FS15i)
RE filter 1 : Damping
2359 (FS30i, 16i)
[Valid data range] 0 (If it is 0, the resonance elimination filer has the conventional
specification.)
1 to 100 (If it is 1, the attenuation ratio is maximized. For resonance
elimination filer 1.)
[Unit of data] %
CAUTION
1 If damping = 0 for resonance elimination filter 1,
this filter has the same specification as for
conventional resonance elimination filters. So, its
attenuation bandwidth can be set only to 20, 30, or
40 Hz (specification compatible with conventional
resonance elimination filters).
2 Resonance elimination filter 1 is enabled if a
nonzero value is set in the attenuation bandwidth
or damping parameter for it. If you do not want use
the resonance elimination filter, reset all the three
parameters (attenuation center frequency,
attenuation bandwidth, and damping) to 0.
[Parameters for resonance elimination filters]
For Series 30i or 16i
Attenuation center
frequency [Hz]
Attenuation
bandwidth
Damping
Resonance elimination filter 2 No.2360 No.2361 No.2362
Resonance elimination filter 3 No.2363 No.2364 No.2365
Resonance elimination filter 4 No.2366 No.2367 No.2368
Resonance elimination filter 1 No.2113 No.2177 No.2359