B-65270EN/05 3. αiS/αiF/βiS SERIES PARAMETER ADJUSTMENT
- 65 -
#7 #6 #5 #4 #3 #2 #1 #0
1808 (FS15i)
TGAL
2003 (FS30i, 16i)
TGAL (#1) 1: The level for detecting the software disconnection alarm is set by
parameter.
1892 (FS15i)
Software disconnection alarm level
2064 (FS30i, 16i)
Standard setting 4: Alarm occurs when motor turns 1/8 of a turn.
Increase this value.
Action 3: This alarm occurs when the absolute position data sent from
the built-in Pulsecoder cannot be synchronized with the
phase data. Remove the Pulsecoder cable with the NC
power switched off and wait for about 10 minutes, then
connect the cable again. If this alarm occurs again, replace
the Pulsecoder.
When an absolute type linear encoder is used with a linear
motor or when a synchronous built-in servo motor is used,
this alarm must be ignored because the detector does not
have phase data. Set the following bit.
#7 #6 #5 #4 #3 #2 #1 #0
1707(FS15i)
APTG
2013(FS30i ,16i)
APTG(#7) 1: Ignores α Pulsecoder software disconnection.
(5) Invalid parameter setting alarm
This alarm is identified from alarm 4.
Alarm 4
DTER CRC STB PRM
Description
1
Invalid parameter setting detected
by servo software
If PRM is set to 1, an invalid parameter setting has been detected by
the servo software. Investigate the cause of the alarm according to
Subsec. 2.1.5, "Actions for Illegal Servo Parameter Setting Alarms."
(6) Other alarms
Alarms are identified from alarm 5. The meanings of the bits are as
follows:
Alarm 5
OFS MCC LDM PMS FAN DAL ABF
Description Action
1 Feedback mismatch alarm 1
1 Excessive semi-closed loop error alarm 2
1 Current offset error alarm 3