5.DETAILS OF PARAMETERS B-65270EN/05
- 368 -
5.1 DETAILS OF THE SERVO PARAMETERS FOR Series 30i,
31i, 32i, 15i, 16i, 18i, 21i, 0i, 20i, Power Mate i (SERIES
90D0, 90E0, 90B0, 90B1, 90B6, 90B5, AND 9096)
The descriptions of parameters follow.
For parameters for which a specification method is not described, do
not change the parameters from the values set up automatically during
servo parameter initialization.
The parameter in the top left cell applies to Series 15i; the one in the
bottom left cell, to Series 30i, 31i, 32i, 16i, 18i, 20i, 21i, 0i, 20i,
Power Mate i.
: Do not change.
#7 #6 #5 #4 #3 #2 #1 #0
1815 (FS15i)
APCX OPTX
1815 (FS30i, 16i)
OPTX (#1) A separate detector is:
0: Used .
1: Not used.
[Reference item] Subsection 2.1.3
APCX (#5) An absolute detector is:
0: Not used.
1: Used .
[Reference item] Subsection 2.1.3
#7 #6 #5 #4 #3 #2 #1 #0
1817 (FS15i)
TANDEM
1817 (FS30i, 16i)
TANDEM (#6) Tandem control (optional function) is:
0: Disabled.
1: Enabled.
Specify this parameter for both main axis and sub-axis.
[Reference item] Section 4.18
#7 #6 #5 #4 #3 #2 #1 #0
1804 (FS15i)
PGEX PRMC DGPR PLC0
2000 (FS30i, 16i)
PLC0 (#0) Specifies whether to multiply the number of velocity and position
pulses by ten internally as follows:
0: Not to multiply by ten.
1: To multiply by ten.
[Reference item] Subsection 2.1.3
DGPR (#1) When power is switched on, the motor-specific standard servo
parameter is:
0: Specified.
1: Not specified.
[Reference item] Subsection 2.1.3