13.ERROR MESSAGES B-66234EN/05
- 452 -
Error code Message Cause/action
I:E-3105 **** Source program format is different. The format of the source program is FORMAT-A.
I:E-3106 **** file read error.
I:E-3107 System parameter read error. A source file containing system parameter data is missing.
I:E-3108 Title read error. A source file containing title data is missing.
I:E-3109 I/O module read error. A source file containing I/O module data is missing.
I:E-3110 Verification error An entered password does not match the set password.
I:E-3111
This word can not be used as password. Try
another word
Try another password.
I:E-3112
Only alphabetical and numerical characters are
allowed
A password including other than alphanumeric characters
was entered.
I:E-3200 There is an undefined instruction.
An instruction that cannot be handled with a selected type
of program is included.
I:E-3201
There is no coil in the functional instruction
which needs the coil.
For a function instruction that requires a coil, no coil is set.
I:E-3220 The **** parameter is out of range.
In a parameter of the **** instruction, a numeric value
outside the specifiable range is specified.
I:E-3221
Program number is different from program
name.
In a parameter of the sub-program start instruction SP, a
program number that does not match the file name is
specified.
I:E-3222
An illegal program number is specified for the
**** instruction.
In a parameter of the **** instruction, a program number
outside the specifiable range or an address other than a
program number is specified.
I:E-3223
An illegal label number is specified for the ****
instruction.
In a parameter of the **** instruction, a label number
outside the specifiable range or an address other than a
label number is specified.
I:E-3250 There is no LADDER program.
The contents of a ladder program are empty. The END1 or
END2 instruction is required.
I:E-3251 The size of LADDER program is too large.
The size of a ladder program exceeds the maximum
specifiable size of a selected type of program.
I:E-3252 LADDER program is broken. An instruction is destroyed and unrecognizable.
I:E-3253
LADDER execution time at the 1st level is too
large.
The execution of the first level of the main program takes
an excessively long time, so that the ladder cannot be
executed. Reduce the first level or increase the value of the
system parameter by specifying a ladder execution time
ratio.
I:E-3254
The number of division of LADDER exceeds
99.
The number of divisions of the second level of the main
program exceeded the maximum allowable value (99), so
that the ladder cannot be executed. Reduce the size of the
second level or increase the value of the system parameter
by specifying a ladder execution time ratio.
I:E-3270
SP instruction can not be used in the main
program.
SP is the sub-program start instruction. SP cannot be used
with a main program.
I:E-3271
SPE instruction can not be used in the main
program.
SPE is the sub-program end instruction. SPE cannot be
used with a main program.
I:E-3272
JMPC instruction can not be used in the main
program.
JMPC is an instruction for making a jump from a
sub-program to the second level of the main program.
JMPC cannot be used with a main program.
I:E-3273
CALL instruction can not be used excluding the
2nd level main program.
No sub-program can be called from a level other than the
second level of the main program. So, the CALL instruction
cannot be used.
I:E-3274
CALLU instruction can not be used excluding
the 2nd level main program.
No sub-program can be called from a level other than the
second level of the main program. So, the CALLU
instruction cannot be used.