10.AUXILIARY FUNCTION B-63943EN-1/02
- 1194 -
10.2 AUXILIARY FUNCTION LOCK
Overview
Inhibits execution of a specified M, S, T and B function. That is, code
signals and strobe signals are not issued. This function is used to
check a program.
Signal
Auxiliary function lock signal AFL<Gn005#6>
[Classification] Input signal
[Function] This signal selects auxiliary function lock. That is, this signal disables
the execution of specified M, S, T, and B functions.
[Operation] When this signal turns to "1", the control unit functions as described
below.
(1) The control unit does not execute M, S, T, and B functions
specified for memory operation, DNC operation, or MDI
operation. That is, the control unit stops the output of code
signals and strobe signals (MF, SF, TF, BF).
(2) If this signal turns to "1" after code signal output, the output
operation is executed in the ordinary manner until its completion
(that is, until the FIN signal is received, and the strobe signal
turns to "0").
(3) Among the auxiliary functions, M00, M01, M02, and M30 are
executed even when this signal is "1". All code signals, strobe
signals, decode signals are output in the ordinary manner.
(4) Among the auxiliary functions, even when this signal is "1",
those functions (M98 and M99) that are executed in the control
unit without outputting their execution results are executed in the
ordinary manner.
CAUTION
Even when this signal is "1", spindle analog output
or spindle serial output is executed.
Auxiliary function lock check signal MAFL<Fn004#4>
[Classification] Output signal
[Function] This signal reports the state of the auxiliary function lock signal AFL.
[Output condition] This signal turns to "1" when:
- The auxiliary function lock signal AFL is "1"
This signal turns to "0" when:
- The auxiliary function lock signal AFL is "0"
Signal address
#7 #6 #5 #4 #3 #2 #1 #0
Gn005 AFL
#7 #6 #5 #4 #3 #2 #1 #0
Fn004 MAFL