1.AXIS CONTROL B-63943EN-1/02
- 148 -
#7 #6 #5 #4 #3 #2 #1 #0
14476 2AX
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Bit
# 1 2AX Servo software 90Dx series for servo HRV4 control is:
0: Not used.
1: Used.
Alarm and message
Number Message Description
SV0456 ILLEGAL CURRENT LOOP An attempt was made to set the current loop that could not
be set.
The amplifier pulse module in use does not comply with
HIGH SPEED HRV. Or, requirements to control are not
satisfied in the system.
SV0458 CURRENT LOOP ERROR The specified current loop differs from the actual current
loop.
SV0459 HI HRV SETTING ERROR For two axes whose servo axis numbers (parameter No.
1023) are
consecutively even and odd numbers, HIGH SPEED HRV
control is possible for one axis and impossible for the other.
SV0460 FSSB DISCONNECT The FSSB connection was discontinued. Or, the FSSB
connection cable was disconnected or broken.
The amplifier was turned off .
In the amplifier, the low-voltage alarm occurred.
SV0462 SEND CNC DATA FAILED The correct data could not be received on a slave side
because of the FSSB communication error.
SV0463 SEND SLAVE DATA FAILED The correct data could not be received in the servo software
because of the FSSB communication error.
SV0465 READ ID DATA FAILED A read of the ID information for the amplifier has failed at
power-on.
SV0466 MOTOR/AMP. COMBINATION The maximum current of an amplifier is different to that of a
motor. Or, the connection command for an amplifier is
incorrect. The parameter setting is incorrect
SV0468 HI HRV SETTING ERROR(AMP) An attempt was made to set up HIGH SPEED HRV control
for use when the controlled axis of an amplifier for which
HIGH SPEED HRV control could not be used.
SV1067 FSSB:CONFIGURATION ERROR(SOFT) An FSSB configuration error occurred (detected by software).
The connected amplifier type is incompatible with the FSSB
setting value.
SV5134 FSSB:OPEN READY TIME OUT In the initialization, the FSSB could not be in an open ready
sate. The axis card is thought to be defective.
SV5136 FSSB:NUMBER OF AMP. IS
INSUFFICIENT
The number of amplifier identified by the FSSB is insufficient
than the number of control axes. Or, the setting of the
number of axes or the amplifier connection is in error.