B-63943EN-1/02 1.AXIS CONTROL
- 151 -
・Differences between the specifications of the FS30i and those of the
FS16i/FS18i/FS21i
With the FS16i/FS18i/FS21i, when bit 1 (XZF) of parameter No. 1807
is set to 0, the coordinate system is established.
At this time, the reference position establishment signals (F120) are
set to “1”, which indicates that the reference position has been
established.
Diagnostic data No. 304 (reference counter value) is also displayed.
With the FS30i, the built-in absolute pulse coder is used to roughly
determine the coordinate position without establishing the coordinate
system.
At this time, the reference position establishment signals (F120) are
set to “0”, which indicates that the reference position has not been
established.
Diagnostic data No. 304 (reference counter value) is not also
displayed.
When manual reference position return by the scale of the full closed
system is completed, the accurate coordinate system is established.
At this time, the reference position establishment signals (F120) are
set to “1”, which indicates that the reference position has been
established.
Diagnostic data No. 304 (reference counter value) is also displayed.
With the FS30i, bit 1 (XZF) of parameter No. 1807 is not provided.
Parameters
#7 #6 #5 #4 #3 #2 #1 #0
1815 APCx APZx OPTx
[Input type] Parameter input
[Data type] Bit axis
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
# 1 OPTx Position detector
0 : A separate pulse coder is not used.
1 : A separate pulse coder is used.
NOTE
In case of using this function, this parameter is set
to "1".