B-63943EN-1/02 1.AXIS CONTROL
- 139 -
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Byte axis
[Valid data range] 0 to 7
Set the connector numbers corresponding to connectors to be
connected when the separate detector interface unit set by parameter
PM3, PM4, PM1, or PM2 (No.1905#1, #2, #6, or #7) is used. The
values to be set are indicated below.
Within one separate detector interface unit, use connector numbers
sequentially. No intermediate number may be omitted.
Correspondence between
connectors and connector numbers
Connector Connector number
JF101 0
JF102 1
JF103 2
JF104 3
JF105 4
JF106 5
JF107 6
JF108 7
Example of setting)
Separate detector connection destination Parameter setting
Controlled
axis
Connectors
for 1st unit
Connectors
for 2nd unit
Connectors
for 3rd unit
Connectors
for 4th unit
No.
1936
No.
1937
No.
1938
No.
1939
No.1905
(#7,#6,#2,#1)
X1 JF101 - - - 0 - - - 0,1,0,0
Y1 - JF102 - - - 1 - - 1,0,0,0
Z1 - - JF102 - - - 1 - 0,0,0,1
X2 - JF101 - - - 0 - - 1,0,0,0
Y2 - - - JF101 - - - 0 0,0,1,0
Z2 - - - - - - - - 0,0,0,0
A1 - - JF101 - - - 0 - 0,0,0,1
B1 - - - JF102 - - - 1 0,0,1,0
C1 - JF104 - - - 3 - - 1,0,0,0
A2 JF102 - - - 1 - - - 0,1,0,0
B2 - JF103 - - - 2 - - 1,0,0,0
C2 - - - JF103 - - - 2 0,0,1,0
NOTE
When automatic setting mode is selected for FSSB
setting (when the parameter FMD (No.1902#0) is set
to 0), these parameters are automatically set when
input is performed with the FSSB setting screen.
When manual setting 2 mode is selected for FSSB
setting (when the parameter FMD (No.1902#0) is set
to 1), these parameters must be set directly.