1.AXIS CONTROL B-63943EN-1/02
- 112 -
Generally, set the middle value between the positioning deviation
limit during movement and the positioning deviation at rapid traverse
as the feed stop positioning deviation.
1850 Grid shift and reference position shift for each axis
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] 2-word axis
[Unit of data] Detection unit
[Valid data range] 0 to 99999999
To shift the reference position, the grid can be shifted by the amount
set in this parameter. Up to the maximum value counted by the
reference counter can be specified as the grid shift.
In case of parameter SFDx(No.1008#4) is 0: Grid shift
In case of parameter SFDx(No.1008#4) is 1: Reference point shift
NOTE
For setting the reference position without dogs,
only the grid shift function can be used.
(The reference position shift function cannot be
used.)