B-63943EN-1/02 4.REFERENCE POSITION ESTABLISHMENT
- 533 -
NOTE
1 On reference point establishment of manual feed
axis for simple synchronous control, if you set this
parameter on either master or slave axis, it
become effective on both master and slave axes
automatically.
2 On angular axis control, this parameter setting of
perpendicular axis is ignored during the reference
position establishment of the angular axis.
Alarm and message
No. Message Description
PS0372 REFERENCE RETURN
INCOMPLETE
An attempt was made to perform an automatic return to the
reference position on the orthogonal axis before the completion of a
return to the reference position on the angular axis.
However, this attempt failed because a manual return to the
reference position during angular axis control or an automatic return
to the reference position after power-up was not commanded. First,
return to the reference position on the angular axis, then return to
the reference position on the orthogonal axis.
PS0376 SERIAL DCL: ILLEGAL
PARAMETER
1. When Parameter No.1815#1 is set to “1”, parameter No.2002#3
is set to “0”
2. The absolute-position detection function is enabled. (Parameter
No.1815#5 is set to “1”. )
PS5220 REFERENCE POINT
ADJUSTMENT MODE
In case of distance coded linear scale I/F, the reference point auto
setting parameter (No.1819#2) is set to "1". Move the machine to
reference position by manual operation and execute manual
reference return.
DS0016 SERIAL DCL:FOLLOW-UP
ERROR
1. The value of parameter No.1883,No.1884 is out of range.
2. The amount of follow-up is more than 2147483647 or less than
-2147483648 on detection unit. To reduce the follow-up amount,
please adjust the point that we begin follow-up.
DS0017 SERIAL DCL:REF-POS
ESTABLISH ERR
The amount of movement for establish reference position was
exceeded the amount of parameter No.14010. Please try again or
change parameter No.14010 larger.
DS0018 SERIAL
DCL:MISMATCH(SSYNC
CTRL)
Master/slave axes of feed axis synchronization control, one of them
is the linear scale with distance-coded reference marks (serial) and
the other of them is not the linear scale with distance-coded
reference marks (serial). Please establish reference position with the
input signal SYNCn<G138>, SYNCJn<G140> or parameter SCA
No.8304#5 setting to 0.
DS0019 SERIAL
DCL:MISMATCH(ANGL-AXIS
)
On angular axis control, one of the angular/perpendicular axes is the
scale with ref-pos, and the other of them is not the scale with
ref-pos. Such system is not admired.
DS0020 REFERENCE RETURN
INCOMPLETE
An attempt was made to perform an automatic return to the
reference position on the orthogonal axis before the completion of a
return to the reference position on the angular axis.
However, this attempt failed because a manual return to the
reference position during angular axis control or an automatic return
to the reference position after power-up was not commanded. First,
return to the reference position on the angular axis, then return to
the reference position on the orthogonal axis.
SV0366 PULSE MISS(INT) A pulse error occurred on the built-in Pulsecoder.
SV0367 COUNT MISS(INT) A count error occurred on the built-in Pulsecoder.
SV0382 COUNT MISS(EXT) A count error occurred on the separate detector.
SV0383 PULSE MISS(EXT) A pulse error occurred on the separate detector.