1.AXIS CONTROL B-63943EN-1/02
- 206 -
8337 M code for turning off synchronization in feed axis synchronous control
[Input type] Parameter input
[Data type] 2-word path
[Valid data range] 1 to 999999999
This parameter specifies an M code for switching from synchronous
operation to normal operation.
The M code set in this parameter is not buffered.
8338 M code for turning on synchronization in feed axis synchronous control
[Input type] Parameter input
[Data type] 2-word path
[Valid data range] 1 to 999999999
This parameter specifies an M code for switching from normal
operation to synchronous operation.
The M code set in this parameter is not buffered.
Notes on setting parameters for each axis
Parameters to be set for each axis can be divided into the following
four types when they are set for an axis under feed axis synchronous
control:
(1) Parameter which must be set to the same value for the master and
slave axes
(2) Parameter which needs to be set only for the master axis (data for
the slave axis is not used.)
(3) Parameter which may be set to different values for the master and
slave axes
(4) Parameter which needs to be set only for the slave axis (data for
the master axis is not used.)
Parameters are listed for each type below. If a parameter is not listed
in any table below, assume that the parameter is of type (1) and set the
same value for the master and slave axes.
CAUTION
1 If different values are set in a parameter of type (1)
for the master and slave axes, these axes may not
operate as axes under feed axis synchronous
control.
2 When a signal is used to switch between
synchronous and normal operation, in a parameter
of type (2), also set a value for each of the master
and slave axes.