B-63530EN/03 4.DESCRIPTION OF PARAMETERS
- 167 -
IO2x A second I/O module supporting FSSB is:
0 : Not used.
1 : Used.
NOTE
1 On the FSSB, an FSSB I/O unit and separate
detector interface unit (pulse module) are handled
as units of the same type. The term "first unit" or
"second unit" used in the descriptions here
represents the ordinal number of a unit counted
without making a distinction between FSSB I/O
units and separate detector interface units. For
example, suppose that one FSSB I/O unit and one
separate detector interface unit are used and that
the separate detector interface unit is connected on
the FSSB closer to the CNC and the FSSB I/O unit
is connected on the FSSB farther from the CNC. In
this case, the FSSB I/O unit is the "second unit".
2 An FSSB I/O unit is controlled with the first servo
axis. For an axis with parameter No. 1023 = 1 (or
with parameter No. 1023 = 9 for tool post 2 under
2-CPU 2-path control or tool post 2 under 2-CPU
3-path control), set IO1 (or IO2) to 1. For other
axes, set IO1 to 0 and IO2 to 0.
PM1x The first separate detector interface unit is:
0 : Not used.
1 : Used.
PM2x The second separate detector interface unit is:
0 : Not used.
1 : Used.
NOTE
When automatic setting mode is selected for FSSB
setting (when the FMD parameter (bit 0 of
parameter No.1902) is set to 0), parameter
No.1905 is automatically set when input is
performed with the FSSB setting screen. When
manual setting 2 mode is selected for FSSB setting
(when the FMD parameter (bit 0 of parameter
No.1902) is set to 1), parameter No.1905 must be
set directly. When a separate detector interface
unit is used, a connector number must be set in the
corresponding parameter (No.1936 or No.1937).