4.DESCRIPTION OF PARAMETERS B-63530EN/03
- 542 -
NCS If an overtravel alarm is issued for an axis under synchronous/
composite or superimposed control, synchronous/composite or
superimposed control is:
0 : Canceled.
1 : Not canceled.
If an overtravel alarm is issued for an axis under synchronous/
composite or superimposed control, the following operation is
performed according to the setting of this parameter:
When NCS is set to 0 P/S alarm No. 255 may be issued together with
the overtravel alarm. In this case, place the machine in the emergency
stop state once, then release the alarm.
When NCS is set to 1. The machine decelerates, then stops with a
delay of 8 msec in comparison with an ordinary overtravel alarm.
NOTE
With the M series, synchronous control only is
enabled.
SPE The synchronous error amount is:
0 : The difference between the positioning deviation of the master
axis and that of the slave axis.
1 : The difference between the positioning deviation of the master
axis and that of the slave axis plus the acceleration/deceleration
delay.
NOTE
When the master and slave axes have different
acceleration/deceleration time constants, set 1.
NRS When the system is reset, synchronous, composite, or superimposed
control is:
0 : Canceled.
1 : Not canceled.
NOTE
With the M series, synchronous control only is
enabled.