Reference point
establishment signal
ZRF1-ZRF8<F120>
(Classification) Output signal
(Function) Notify the system that the reference position has been established.
A reference position established signal is provided for each axis. The
number appended to each signal name indicates the number of the
controlled axis.
ZRF1
1: 1st-axis reference position establishment signal
2: 2nd-axis reference position establishment signal
3: 3rd-axis reference position establishment signal
:
:
(Output condition) The signals are set to 1 in the following case.
・ When the reference position is established after manual
reference position return.
・ When the reference position is established using the
absolute-position detector at initial power-on.
The signals are set to 0 in the following case.
・When the reference position is lost.
Note)
The new specification is selected by the parameter No.1203#1=1.
In the new specification comparing with the conventional specification, the condition to
turning on/off the reference point establishment signals (ZRF1-ZRF8) is different at the
following points.
•
•
All the bits are turned off during following up the absolute position detector. The
bits corresponding to the axes established the reference point (the axis whose
parameter 1815#4(APZ) is set to 1) are turned on automatically.
While an APC / SPC alarm occurs, the bit corresponding to the alarm axis is
turned off. But in case of an alarm 307 or 308 (battery low alarm1, 2), the bit is
not turned off. The bit, that is turned off by an APC / SPC alarm, is turned on
again if the parameter No.1815#4(APZ) of the axis is 1 after releasing alarm.
#7 #6 #5 #4 #3 #2 #1 #0
F120 ZRF8 ZRF7 ZRF6 ZRF5 ZRF4 ZRF3 ZRF2 ZRF1
Ed
Page
12 / 26
Date Sign
Contents
FANUC Power Mate i-MODEL D/H
High Speed Position Switch
specifications
B-63173EN-1/01-31
TITLE
DRAWING