B-63950EN/02 4.DESCRIPTION OF PARAMETERS
- 103 -
When *FLWU is 0, follow-up is performed.
When *FLWU is 1, follow-up is not performed.
1: Follow-up is not performed.
NOTE
When using the index table indexing function, set
FUPx to 1 for a control axis subject to index table
indexing.
# 1 CRFx When the servo alarm SV0445 (soft disconnection), SV0447 (hard
disconnection (separate)), or SV0421 (dual position feedback
excessive error) is issued:
0: The reference position established state is not affected.
1: The reference position unestablished state is assumed. (Bit 4
(APZ) of parameter No. 1815 is set to 0.)
# 2 DATx When a linear scale with an absolute address zero point or a linear
scale with absolute address reference marks is used, the automatic
setting of parameter No. 1883 and No. 1884 at manual reference
position return time is:
0: Not performed.
1: Performed.
The automatic setting procedure is as follows:
<1> Set an appropriate value in parameter No. 1815, No. 1821, and
No. 1882.
<2> Position the machine at the reference position by manual
operation.
<3> Set this parameter to 1.
<4> Perform a manual reference position return operation. Upon
completion of manual reference position return operation,
parameter No. 1883 and No. 1884 are set, and this parameter is
automatically set to 0.
# 7 NAHx In the advanced preview control mode, advanced preview
feed-forward is:
0: Used
1: Not used
1820 Command multiplier for each axis (CMR)
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
[Input type] Parameter input
[Data type] Byte axis
[Valid data range] See below :
Set a command multiplier indicating the ratio of the least command
increment to the detection unit for each axis.
Least command increment = detection unit × command multiplier