4.DESCRIPTION OF PARAMETERS B-63950EN/02
- 434 -
4.60 PARAMETERS OF MAINTENANCE
#7 #6 #5 #4 #3 #2 #1 #0
8900 PWE
[Input type] Setting input
[Data type] Bit
# 0 PWE The setting, from an external device and MDI panel, of those
parameters that cannot be set by setting input is:
0: Disabled.
1: Enabled.
#7 #6 #5 #4 #3 #2 #1 #0
8901 MEN FAN
[Input type] Setting input
[Data type] Bit path
# 0 FAN A fan motor error is:
0: Detected.
1: Not detected.
NOTE
Be sure to set this parameter to 0.
# 7 MEN The periodic maintenance screen is:
0: Displayed.
1: Not displayed.
8911 Percentage for life warning display on the periodic maintenance screen
[Input type] Parameter input
[Data type] Byte path
[Unit of data] %
[Valid data range] 0 to 99
On the periodic maintenance screen, if the remaining time of an item
falls to a value less than the percentage of the life specified in this
parameter, the item name and remaining time is displayed in red as a
warming.
#7 #6 #5 #4 #3 #2 #1 #0
8950 MEM
[Input type] Parameter input
[Data type] Bit
# 0 MEM The memory contents display screen is:
0: Not displayed.
1: Is displayed.