FANUC PMC-MODEL SD7
Programming Manual
01 01.11.26
Hanaoka
New
A-78550E
EDIT DATE DESIG.
DESCRIPTION
195/
316
TITLE
DRAW.NO.
sr: DINT variable; the first element of the source array.
snx: UINT, variable or constant; the index into the source array.
dnx: UINT, variable or constant; the index into the destination array.
n: UINT, variable or constant; count indicator.
ds: DINT variable; the first element of the destination array.
length: Constant; the number (1 - 32767) of elements (starting at 'sr' and 'ds') that make up each array.
4.7.1.4 ARRAY_MOVE_BOOL( sr, snx, dnx, n, length, ds)
When the function receives power flow, the number of data elements in the count indicator 'n' is extracted from the
input array starting with the indexed location ('sr' + 'snx' – 1). The data elements are written to the output array starting
with the indexed location ('ds' + 'dnx' – 1).
sr: BOOL, variable; the first element of the source array. For an Array Move with the data type BOOL, any reference
may be used; it does not need to be byte aligned.
snx: UINT, variable or constant; the index into the source array.
dnx: UINT, variable or constant; the index into the destination array.
n: UINT, variable or constant; count indicator.
ds: BOOL, variable; the first element of the destination array. For an Array Move with the data type BOOL, any
reference may be used. It does not need to be byte aligned.
length: Constant; the number (1 - 32767) of elements (starting at 'sr' and 'ds') that make up each array.
4.7.1.5 ARRAY_MOVE_BYTE( sr, snx, dnx, n, length, ds)
When the function receives power flow, the number of data elements in the count indicator 'n' is extracted from the
input array starting with the indexed location ('sr' + 'snx' – 1). The data elements are written to the output array starting
with the indexed location ('ds' + 'dnx' – 1).
sr: BYTE variable; the first element of the source array.
snx: UINT, variable or constant; the index into the source array.
dnx: UINT, variable or constant; the index into the destination array.
n: UINT, variable or constant; count indicator.
ds: BYTE variable; the first element of the destination array.
length: Constant; the number (1 - 32767) of elements (starting at 'sr' and 'ds') that make up each array.
4.7.1.6 ARRAY_MOVE_WORD( sr, snx, dnx, n, length, ds)
When the function receives power flow, the number of data elements in the count indicator 'n' is extracted from the
input array starting with the indexed location ('sr' + 'snx' – 1). The data elements are written to the output array starting
with the indexed location ('ds' + 'dnx' – 1).
sr: WORD variable; the first element of the source array.